SoliTherm Outdoor air conditioning unit OC-5715-230V. All our UL type 4X units come with a condensate evaporation and a cabinet heater.
Product Feature
| Order Number | 57150182 |
| Brand Name | Compact Outdoor |
| Colour | RAL 7035 |
| Housing Material | Stainless steel AISI 304 (V2A) |
| IP protection class to EN 60 529 | IP 56 / Type 12, 3, 3R, 4 |
| Included | With enclosure heater and aluminium filter |
| Approvals | CE, cURus, cULus |
| UL File Number | cURus (SA32278), cULus (E498756) |
Technical Data
| Cooling capacity L35L35 (EN14511-3) | 1500 W @ 50 Hz 1500 W @ 60 Hz |
| Cooling capacity L35L50 (EN14511-3) | 1250 W @ 50 Hz 1280 W @ 60 Hz |
| Enclosure heater | 1000 W |
| Compressor type | Rotary Piston Compressor |
| Refrigerant / GWP | R513A / 630 |
| Refrigerant charge | 558 g / 19.7 oz |
| High / low Pressure | 26 / 6 bar 383 / 88 psig |
| Air flow volume (system / unimpeded) | Ambient air circuit: 655 / 1200 m³/h Cabinet air circuit: 400 / 550 m³/h |
| Operating Temperature Range | -40°C - 55°C |
| Mounting | Wall mounted |
| Dimensions A x B x C (D+E) A = Height | B = Width | C = Depth | 1,150 x 395 x 270 mm |
| Weight | 42 kg |
| Voltage / Frequency | 230 V ~ 50/60 Hz |
| UL Voltage / Frequency | 230 V ~ 60 Hz |
| Current L35L35 | 3.7 A @ 50 Hz 4.3 A @ 60 Hz |
| Starting current | 16 A |
| Max. current | 7.1 A |
| Nominal power L35L35 | 801 W @ 50 Hz 961 W @ 60 Hz |
| Max. power | 992 W @ 50 Hz 1175 W @ 60 Hz |
| Fuse | 12 A (T) |
| Short-circuit current rating | 5 kA |
| Connection | 4-pole terminal block for power 5-pole terminal block for signals 3-pole terminal block for RS 485 |